R-ECO - Emergency center

Only when moving walks over 40 meters

According to DIN EN 115-1:2018-01 Section 5.12.2.2.3.1, the moving walkways have to be equipped with clearly visible manual emergency shutdowns, which will enable to stop the moving walkway in an emergency immediately. So that these emergency shutdowns are easily accessible, the mounting is recommended at the beginning and end of the moving walkways. The visual design is arranged in section 7.2.1.2.2.

With long moving walkways the distances between the emergency shutdowns must not exceed 40m.

At bigger distances, additional emergency stops need to be built in (preferably in the middle). The position of the emergency stop, for moving walkways, which are passable with purchasing- or baggage carts are regulated in Section I.2.